GRIDlink ST-IPM 6350 Series Specifications
Product Applications
- Scalable ADR Controller
- Grid Connected Solar Field Controller
Industrial powerPC (32 bit data bus)
- Operating system embedded Linux
- Static memory (RAM) 2 Mbytes – 32bit, 0 wait states
- Dynamic memory (RAM) 64 Mbytes – 32bit, 0 wait states
- Program memory (Flash) 128 Mbytes
- Retained memory (RAM) 2 Mbytes (battery-backed)
- Real-time clock battery-backed for time stamping and other operations
- I/O Expansion RS-485 or Ethernet
- Maximum distributed I/O 5,000+ (application dependent)
- Data logging
ETHERNET PORTS (All)
- 10/100BaseTx (auto-detecting)
- RJ45 connection (auto-crossover)
- Protocols TCP / IP, ARP, UDP, ICMP, DHCP, Modbus / TCP, optionally PPP, DNP3, IEC60870-5-101/104 and more
- Two Independent networks with unique MAC and IP addresses
- Network port 1 – (1) shielded RJ45 connector
- Network port 2 – (4) shielded RJ45 connectors (linked
via integrated Ethernet switch)
SERIAL PORT
- Up to 115,200 baud
- RS232 Port A RJ45 (TD, RD, CTS, RTS, CD,TR, DSR, GND)
- RS232 Port B RJ45 (TD, RD, CTS, RTS, CD, DTR, DSR, GND)
- RS485 Port C Screws (485+, 485-, GND) (2-wire halfduplex)
- Protocols (master & slave) Modbus RTU/ASCII, Optional DNP3 slave, IEC60870-5-101/104.
ENVIRONMENTAL
- DIN rail or flat panel mount
- Input power 10-30 VDC
- Input current 150 mA @ 24 VDC (typical)
- Temperature -40 to 70°C (-40 to 85°C storage)
- Humidity 5% to 95% RH (non-condensing)
- Flammability UL 94V-0 materials
- Electrical Safety UL 508, CSA C22.2/14; EN61010-1
(IEC1010); CE - EMI emissions FCC part 15, ICES-003, Class A;
EN55022; EN61326-1; CE - EMC immunity EN61326-1 (EN61000-4-2,3,4,6); CE
- Surge withstand IEEE-472 (ANSI C37.90)
- Vibration IEC68-2-6
- Hazardous locations (Class 1, Div 2, Groups A,B,C,D) UL 1604, CSA C22.2/213, Cenelec EN50021 Zone 2
- Tested to Marine/offshore standards