Modbus I/O Transfers – Shark

by | Nov 5, 2017 | Power Meters Shark-Group

I/O Transfers
Action Def
Registers
Comm Setup

GRIDlink can poll up to 4 meters of any type and can use Modbus RTU (RS485) or TCP over Ethernet

The polls capture 15 Float Output Modbus registers starting from the Shark Modbus Address 40999

FI 500 Shark1_1 Volts A-N meter #1
FI 501 Shark1_2 Volts B-N meter #1
FI 502 Shark1_3 Volts C-N meter #1
FI 503 Shark1_4 Volts A-B meter #1
FI 504 Shark1_5 Volts B-C meter #1
FI 505 Shark1_6 Volts C-A meter #1
FI 506 Shark1_7 Amps A meter #1
FI 507 Shark1_8 Amps B meter #1
FI 508 Shark1_9 Amps C meter #1
FI 509 Shark1_10 WATTS 3-Ph total meter #1
FI 510 Shark1_11 VARs 3-Ph total meter #1
FI 511 Shark1_12 VAs 3-Ph total meter #1
FI 512 Shark1_13 Power Factor 3-Ph total meter #1
FI 513 Shark1_14 Frequency meter #1

 

and place them in Float Input Virtual I/O Modules

Shark1    – FI500 thru 514

Shark2    – FI550 thru 564

Shark3    – FI600 thru 614

Shark4    – FI650 thru 614