Wiring Series 113/135 – Lighting Controls
LC-24-RELAY
Dry Contact for Demand Response Lighting Controls
Principle of Operation:
- The Lighting Controls send a DC signal to the dry contact closure and senses the return signal reducing the light level when that signal is present to respond to a Demand Response Event.
LC-24-001
Achieves Pre-set for 0-10V output for Demand Response Lighting Controls
Principle of Operation:
- The power supply V1 is assumed to be 24VDC.
- When in Event, terminal 8 High Relay Output is 24V
- When not in Event, terminal 8 High Relay Output is 0V
- Adjusting R2 Potentiometer on installation reduces voltage output to achieve desired voltage to meet lighting reduction
- Voltage output varies based on wire run distance and controller load
- Maximum Output is 1A
LC-24-002
Achieves Pre-set for 0-10V output for Demand Response Lighting Controls with Event/No Event adjustable voltage outputs
Principle of Operation:
- The power supply V1 is assumed to be 24VDC.
- When in Event, terminal 8 High Relay Output is 24V
- When not in Event, LC-24-002 offers adjustable 5-24V Output
- Adjusting R2 Potentiometer on installation reduces voltage output to achieve desired voltage to meet lighting reduction
- Voltage output varies based on wire run distance and controller load
- Maximum Output is 1A