E Series configuration to obtain Modbus meter data via Ethernet.

Floating Point Modbus Registers

User Defined Tags

Automation > Tags

GRIDlink RAM Modbus Tags create

Click on image to enlarge

Modbus Registers 501-600 are reserved for up to 4 meters with 25 registers per meter to allow additional meter data elements to be user added.

Modbus Remote Stations

GRIDlink E series add new meter

Automation > Modbus > Remote Stations

Add Modbus Meter

Create a remote station for each Modbus meter.

Fill in meter settings.

Click on image to enlarge

GRIDlink E Series Remote Stations

Click on image to enlarge

Modbus I/O Transfer

GRIDlink E Series Modbus transfers add-1

Click on image to enlarge

Automation > Modbus > I/O Transfers

+ Add

Add a Modbus transfer to meter.

Fill in settings.

GRIDlink E Series Modbus IO tranfer

Click on image to enlarge